Refuge Design and PRM Evacuation at Railway Stations

Refuges and evacuation arrangements for persons of restricted mobility at new and existing railway stations, under BS 9992:2020, the code of practice for fire safety in rail infrastructure.

When you need it

A step-free access scheme brings people into a station who may not be able to use the stairs or escalators to escape. A new station, a new lift or a capacity upgrade changes how they would be evacuated in a fire. A refuge is where that evacuation pauses safely: a protected place where a person waits, in contact with staff, until assisted evacuation continues. For a railway station the governing code of practice is BS 9992:2020, and its recommendations for persons of restricted mobility, including refuges, are in Clause 16.

What BS 9992 recommends

  • A refuge is a pause, not a destination. The commentary on BS 9992:2020 Clause 16.2 treats a refuge as a place where the evacuation sequence pauses for a limited time, not a place for extended waiting. Refuges are not acceptable in unstaffed stations.
  • Sizing comes from the train. Each refuge should hold the calculated number of wheelchair spaces. The calculation assumes that every wheelchair space on the train on fire is filled, using the rolling stock scheduled to call with the most such spaces, and that the same number of wheelchair users is waiting on the platform, for all lines it serves. At an island platform, the worked note adds the designated spaces of the trains serving the other face. Intermediate refuges, such as those on a concourse, hold the sum of the refuges they serve.
  • Open-air platform refuges. Where platform refuges are in the open air (open to the sky, or under open-sided canopies that cover the platform but not the track), at least two should serve each platform. They should be separate from each other, each as close as reasonably practicable to a different platform exit, and far enough apart that a train fire would not compromise more than one (Clauses 16.2 and 16.4.1). They take the dimensions and other safety features of BS 9999:2017 Annex G but may omit the fire-resisting enclosure.
  • Refuges within buildings follow BS 9999:2017 Annex G in full (Clause 16.2).
  • Communication. BS 9992:2020 recommends emergency voice communication systems to BS 5839-9 at refuges (Clause 16.4.1), so that a person waiting can talk to the staff organising the evacuation. BS 5839-9:2021 covers emergency voice communication systems used to communicate with people in refuges, including refuge communication systems, also known as disabled refuge systems.

Escape capacity for everyone else is calculated to Clauses 14.6 and 14.7. See our BS 9992 fire strategy for railway stations page.

What we do

We prepare Equal Egressibility Strategy reports for railway stations: a quantitative pedestrian movement calculation under BS 9992:2020 Clause 14, refuge provision sized for worst-case PRM presence, escape routes engineered through to a place of safety, and fire and rescue service intervention facilities co-ordinated with the London Fire Brigade.

Existing sub-surface stations raise the practical engineering: vertical evacuation against gravity, evacuation routes engineered within the existing built form, and reliance on emergency-services intervention for the final phase of an incident. Each factor is engineered against the asset, not assumed.

On TfL’s equal egressibility and EVC upgrade programme across eight in-service Jubilee Line Extension sub-surface stations, JWCS authored the Options Development Report and the portfolio-level Technical Requirements Specification, and co-ordinated the refuge point design, the compartmentation upgrades, and the evacuation and intervention modernisation using the BS 9992:2020 refuge methodology. Standardised refuge point signage was developed with TfL Design. The project page sets out the role in full.

On London Underground

Changes to fire precautions at London Underground stations and shafts where London Underground is the Responsible Person are managed through the S1088 change-control process; our S1088 submission checklist sets out what a submission needs. A planned or known departure from a London Underground standard needs an S1641 concession.

How we work

  1. Designate the station and each platform as surface, enclosed or sub-surface.
  2. Establish the PRM demand from the rolling stock and the platform layout.
  3. Size and locate the refuges to BS 9992:2020 Clause 16.2.
  4. Engineer the routes from each refuge to a place of safety, and the assisted evacuation and intervention arrangements, co-ordinated with the London Fire Brigade.
  5. Specify the communication and signage for each refuge.
  6. Feed the outputs into the station fire strategy, any S1088 submission and the operator’s evacuation procedure.

Railway stations, not buildings

BS 9992:2020 draws on BS 9999:2017 for refuge construction, dimensions and safety features (Annex G) and for evacuation lifts, but the number of refuge spaces for platform evacuation, and the evacuation basis at a station, stay with BS 9992. Our article BS 9992 or BS 9999: which code governs your fire strategy? explains how the two codes divide.

Typical deliverables

  • Equal Egressibility Strategy report
  • Refuge area design and provision schedule
  • Quantitative evacuation calculation
  • Options Development Report and Technical Requirements Specification for upgrades to existing stations
  • PRM intervention plan and emergency-services liaison brief
  • Inputs to the station fire strategy and to S1088 submissions

Governing Framework

BS 9992:2020BS 9999:2017 Annex GBS 5839-9:2021Equality Act 2010S1088S1641

Lifecycle stages

Engaged at GRIP 3-5 / Pathway 1-4 / RIBA 2 for new-build; engaged ad hoc for retrofit, accessibility upgrades and station capacity programmes.