Fire Safety at Sub-Surface Railway Stations

Fire strategy inputs, design validation and assurance at sub-surface railway stations, where the Fire Precautions (Sub-surface Railway Stations) (England) Regulations 2009 apply alongside BS 9992:2020.

STREET LEVEL Station entrance To street Stair CONCOURSE Escalator PLATFORM Protected escape route STREET LEVEL Station entrance To street Stair CONCOURSE Escalator PLATFORM Protected escape route
Schematic section, not to scale. Generic illustration, not a specific station.

When the 2009 Regulations apply

The Fire Precautions (Sub-surface Railway Stations) (England) Regulations 2009 (SI 2009/782) apply where premises are used as a railway station, members of the public have access, and there is a railway platform in the premises “which is an enclosed underground platform” (Regulation 3(1)). Both limbs are defined:

  • a platform is enclosed if it and the permanent way beside it are “situated wholly or mainly in a tunnel or wholly or mainly within or under any building” (Regulation 3(2)), where “mainly” means covered by any part of a tunnel or building for more than half the length of the platform (Regulation 3(4)); and
  • a platform is underground if the roof or ceiling immediately above the platform and the adjacent permanent way is below the level of the surface of the ground adjacent to any exit from the station that provides a means of escape in case of fire (Regulation 3(3)).

The test is applied to each platform from the levels and sections of the station. If any one platform is an enclosed underground platform, the Regulations apply to the station premises.

What the Regulations add

Made under article 24 of the Regulatory Reform (Fire Safety) Order 2005, the Regulations set specific fire precautions for sub-surface stations alongside the general fire precautions under the Order. They cover:

  • keeping locked the doors off escape routes that are not part of the means of escape;
  • automatic means of fighting fire in specified rooms (switchgear, storage and shops), with a plan for firefighters;
  • automatic fire detection, an electrical fire warning system, a public address system and staff radio or telephone;
  • keeping the premises clear of combustible matter;
  • the materials of internal walls and ceilings in public areas;
  • staff instruction, training and fire drills; and
  • additional precautions, including supervising contractors’ work and keeping at least two staff on duty when the public has access.

The duties fall on the occupier (Regulation 12). The fire and rescue authority may grant the occupier a written exemption, with or without conditions, from four requirements (Regulations 5(2), 6(2), 9(8) and 10(2)) where it is satisfied that compliance is inappropriate, unnecessary or not reasonably practicable (Regulation 11).

What BS 9992 recommends at sub-surface stations

BS 9992:2020 is the code of practice for the station. At sub-surface stations it recommends:

  • escape capacity for platforms to be cleared within 4 minutes, with travel from the most remote point on the platform to a place of ultimate safety or a protected route within 6 minutes (Clause 14.6);
  • fire resistance of not less than R 120 for elements of structure at sub-surface stations and shafts serving tunnels, whether or not sprinklers are installed (Clause 44.2.1); and
  • reaction to fire recommendations for sub-surface locations (Clause 36), read with the materials requirements of Regulation 8.

On London Underground

S1086 records the classification of each London Underground station and shaft, including whether the 2009 Regulations apply, and a separate classification under BS 9992. At sub-surface stations covered by the Regulations and listed in S1086, the full set of S1085 materials requirements applies, subject to the relaxations S1085 itself allows; our S1085 materials compliance page explains how that is evidenced.

Changes to fire precautions at stations and shafts where London Underground is the Responsible Person are managed through S1088. Under S1088, the TfL Fire Compliance Team is the single point of contact with the London Fire Brigade for change applications at stations (Clause 3.1.7), and it applies to the Brigade for any exemption under the 2009 Regulations (Clause 3.6.2). At sub-surface stations, where the Brigade has served Alteration Notices under the Order, the Fire Compliance Team notifies the Brigade of changes (Clause 3.5.2). Consultation on fire engineering design and fire strategy goes through TfL’s Principal Fire Engineer (Clause 3.1.8). A planned or known departure from a London Underground standard needs an S1641 concession.

Outside London Underground, the Regulations apply to any station in England that meets the Regulation 3 test, whoever operates it. TfL’s Category 1 standards are London Underground’s own and apply to works on its premises by their own scope; where a station adjoins or is integrated with London Underground premises, the interface is assessed case by case.

The related projects listed with this page are all sub-surface stations, and the roles differ. At Bond Street (January 2020 to October 2022), the work covered quality and field assurance of the fire disciplines through to handover, including co-authoring the integrated fire strategy, fire compliance plans, S1088 applications and concession submissions. At Tottenham Court Road (July 2016 to January 2020), the fire detection systems package was led from detailed design through commissioning to handover. At the Belgrove House Ticket Hall, Kings Cross St Pancras, JWCS validated the fire strategy report and detailed design and supported the S1088 approvals through the TfL Fire Compliance Team. On TfL’s Jubilee Line Extension equal egressibility and EVC programme, JWCS authored the Options Development Report and the portfolio-level Technical Requirements Specification for eight in-service sub-surface stations. Each project page sets out the role in full.

What we do

We bring independent fire engineering assurance to sub-surface station projects: fire strategy inputs, validation of fire strategies and detailed design against the governing framework, materials compliance review, S1088 submission support, and field assurance through construction to handover.

How we work

  1. Designate the station. Apply the Regulation 3 test to each platform; on London Underground, read the station’s S1086 classification in full.
  2. Set the sub-surface benchmarks: escape capacity, fire resistance and materials, under BS 9992:2020 and the Regulations.
  3. Confirm the standards that apply by their own scope, and the route for any change or departure.
  4. Validate the design against the fire strategy and the governing framework.
  5. Assure the installation through construction, Authority to Use and handover.

Typical deliverables

  • Fire strategy inputs for sub-surface stations: designation under Regulation 3 (and, on London Underground, the S1086 classification), escape capacity, fire resistance and materials
  • Validation of fire strategy reports and detailed design
  • Materials Compliance Register review
  • S1088 submission support
  • Field assurance through construction to handover

Governing Framework

Fire Precautions (Sub-surface Railway Stations) (England) Regulations 2009Regulatory Reform (Fire Safety) Order 2005BS 9992:2020S1085S1086S1088S1641

Lifecycle stages

Engaged across any single GRIP / Pathway / RIBA stage or end to end across all stages.

Related projects

Insights

Part of our Fire Engineering Assurance service.

Discuss this service

Senior-led from the first conversation.

Contact